Cooling towers: range, approach and why they decide chiller efficiency

2 min read

A water-cooled chiller is only as efficient as the water its cooling tower sends back. Colder condenser water means less work for the compressor, so the tower quietly controls a large share of the plant's electricity use.

Range and approach

  • Range is how much the tower cools the water: water in minus water out.
  • Approach is how close the leaving water gets to the outdoor wet-bulb temperature. A tower can never cool water below wet-bulb, and a smaller approach needs a bigger tower.
  • In Thailand's hot, humid climate the wet-bulb temperature is high for much of the year, so every degree of approach matters.

Why it matters for the chiller

As a rule of thumb, each 1 °C reduction in condenser water temperature cuts chiller energy by roughly 2–3%, within the limits the chiller manufacturer allows. A tower with scaled fill or poor airflow can easily lose several degrees.

Water treatment is an efficiency issue

  • Scale on condenser tubes acts as insulation; even a thin layer raises compressor power noticeably.
  • Corrosion shortens the life of tubes, basins and pipework.
  • Biological growth fouls the fill and is a health risk, including Legionella.
  • Good treatment controls all three while limiting the water lost to blowdown.

What to check

  • Fill, nozzles and drift eliminators: clean, intact and evenly wetted.
  • Fans and drives: belts, gearboxes, vibration, and speed control.
  • Basin level, make-up valve and blowdown rate.
  • Approach at a known load, compared with the tower's design figure.
  • Condenser tube cleanliness, by the chiller's condenser approach temperature.

Controls that save energy

  • Variable-speed tower fans instead of on/off cycling.
  • Running more cells at lower fan speed rather than fewer at full speed.
  • Resetting condenser water temperature with wet-bulb, balancing tower fan energy against chiller energy.

Our CPMS optimises towers, pumps and chillers together, because the lowest plant kW/TR is rarely the point where any one of them is at its own best.