A water-cooled chiller is only as efficient as the water its cooling tower sends back. Colder condenser water means less work for the compressor, so the tower quietly controls a large share of the plant's electricity use.
Range and approach
- Range is how much the tower cools the water: water in minus water out.
- Approach is how close the leaving water gets to the outdoor wet-bulb temperature. A tower can never cool water below wet-bulb, and a smaller approach needs a bigger tower.
- In Thailand's hot, humid climate the wet-bulb temperature is high for much of the year, so every degree of approach matters.
Why it matters for the chiller
As a rule of thumb, each 1 °C reduction in condenser water temperature cuts chiller energy by roughly 2–3%, within the limits the chiller manufacturer allows. A tower with scaled fill or poor airflow can easily lose several degrees.
Water treatment is an efficiency issue
- Scale on condenser tubes acts as insulation; even a thin layer raises compressor power noticeably.
- Corrosion shortens the life of tubes, basins and pipework.
- Biological growth fouls the fill and is a health risk, including Legionella.
- Good treatment controls all three while limiting the water lost to blowdown.
What to check
- Fill, nozzles and drift eliminators: clean, intact and evenly wetted.
- Fans and drives: belts, gearboxes, vibration, and speed control.
- Basin level, make-up valve and blowdown rate.
- Approach at a known load, compared with the tower's design figure.
- Condenser tube cleanliness, by the chiller's condenser approach temperature.
Controls that save energy
- Variable-speed tower fans instead of on/off cycling.
- Running more cells at lower fan speed rather than fewer at full speed.
- Resetting condenser water temperature with wet-bulb, balancing tower fan energy against chiller energy.