Technology

Chiller plant maintenance checklist: daily to annual tasks

3 Nov 2026
Technical
Chiller plant maintenance checklist: daily to annual tasks

2 min read

Good maintenance keeps a chiller plant efficient as well as running. Many of the tasks below have a direct effect on energy use, so they belong in the energy plan as much as the maintenance plan. Always follow the manufacturer's instructions for your specific equipment.

Daily and per shift

  • Log chilled-water and condenser-water supply and return temperatures.
  • Log chiller load, power draw and refrigerant pressures; compare with normal values.
  • Check for alarms, unusual noise, vibration or leaks.
  • Confirm cooling-tower fans, pumps and water levels are normal.

Logged data is what lets you spot a slow drift in efficiency before it becomes a failure. Automated monitoring does this continuously.

Weekly to monthly

  • Check water treatment: conductivity, chemical levels and blowdown on the condenser loop.
  • Inspect cooling towers for scale, debris, algae and uneven water distribution.
  • Check pump and motor bearings, couplings and seals.
  • Clean strainers and check differential pressures.
  • Review kW/TR trends for the plant and each chiller.

Quarterly to half-yearly

  • Test safety controls and alarms.
  • Check refrigerant charge and look for leaks.
  • Inspect electrical connections, starters and drives.
  • Calibrate key temperature, flow and power sensors; bad sensor data leads to bad control decisions.

Annually

  • Clean condenser tubes (and evaporator tubes where needed); fouling raises energy use.
  • Oil analysis and compressor inspection as recommended by the manufacturer.
  • Overhaul cooling towers: fill, drift eliminators, nozzles and fan components.
  • Review control sequences and setpoints against the past year's data.
  • Update the plant's efficiency baseline.

Keep records

Maintenance logs, sensor calibration records and energy data are the evidence that the plant is in good condition. They matter for warranty, insurance, resale and any performance contract.

Maintenance under Cooling-as-a-Service

In a Cooling-as-a-Service contract the provider owns and maintains the plant, so this checklist becomes its responsibility, together with spare parts, insurance and 24/7 monitoring. At Infinity CoolMaster, predictive fault detection in our CPMS flags anomalies before they become failures, and a minimum 10% energy saving is guaranteed in writing.

ShareLINELinkedInFacebook